INTEGRA 128 Plus
EN50131 Grade 3 compliant alarm control panel main board, with 16 up to 128 zones and outputs
Due to their full compliance with the requirements of EN50131 Grade 3, the INTEGRA Plus control units are perfectly fit for implementation of advanced security systems at locations with particularly high risk of burglary, such as banks, jewellery stores or public utility facilities. The control units are characterised by extended functionality, due to which they can be used for implementation of access control systems or even intelligent building solutions.
- full compliance with EN50131 series of standards for Grade 3 equipment
- built-in advanced 2 A+1.5 A power supply with extended autodiagnostics
- up to 128 zones with programmable EOL value and support for 3 EOL configuration
- USB port for programming via PC
- up to 32 partitions, 8 objects
- up to 128 fully programmable outputs
- dedicated buses for communication with keypads and expansion modules
- system operation via touchscreen keypads, LCD keypads, partition keypads, remote control keyfobs or proximity cards
- remote system operation with PC, smartphone or voice-guided telephone menu
- 64 independent timers for automatic control
- access control and home automation features
- non-volatile event log with 22,527 entries, with on-line printing support
- support for 240+8+1 user codes
- firmware upgrades via PC
- option of not reporting possible problems with connecting to the SATEL server as a failure
The actual appearance of the products may differ from the presented images. Product descriptions are provided in the web service for information purposes only.
Documentation
programming
updated: 2022-12-13
1.03 MB
user manual
updated: 2022-12-09
1.89 MB
installer manual
updated: 2022-12-08
1.22 MB
Software
English
compiled: 2023-04-18
multi-language
compiled: 2024-12-12
English
compiled: 2024-10-18
multi-language
compiled: 2024-11-19
4.09 MB
multi-language
compiled: 2024-10-18
English
compiled: 2024-09-25
multi-language
compiled: 2014-02-27
Certificates
EN-50131 GRADE 3 - certificate
updated: 2022-04-25
2.08 MB
EU declaration of conformity
updated: 2024-06-10
115 KB
Technical Data
Low current programmable outputs rating
50 mA
High current programmable outputs rating
3000 mA
Board dimensions
264 x 134 mm
Operating temperature range
-10…+55 °C
Supply voltage (±15%)
20 V AC, 50-60 Hz
Current consumption from battery - standby
130 mA
Recommended transformer type
75 VA
Battery failure voltage threshold (±10%)
11 V
Battery cut-off voltage (±10%)
10,5 V
Environmental class according to EN50130-5
II
Current consumption from the 230V network in standby
135 mA
Maximum current consumption from the 230V network
400 mA
Users + Administrators
240 + 8
Maximum current consumption from the battery
200 mA
Maximum battery charging current
1500 mA
Power supply current efficiency (supplying devices + charging batteries)
2000 + 1500 mA
Power supply output voltage
10,5…14 V DC
Carrying capacity of the +KPD output (±10%)
3000 mA
Carrying capacity of the +EX1 and +EX2 outputs (±10%)
3000 mA
Programmable wired inputs
16
Maximum number of programmable inputs
128
Programmable wired outputs
16
Maximum number of programmable outputs
128
Extender circuits
up to 64
Telephone numbers for notification (voice/PAGER + SMS)
16 + 16
Installer-defined text messaged
64
Security grade according to EN 50131
Grade 3
Information materials
1catalogue
2leaflet - end user
3leaflet - installer
4technical data
5product data sheet